ENSELV (safety extra-low voltage) 
voltage not exceeding 50 V a.c. or 120 V ripple free d.c. between conductors or between conductors or earth in a circuit which is isolated from the supply by means such as a safety isolating transformer

NOTE 1 Maximum voltages lower than 50 V a.c. on 120 V ripple free d.c. may be specified in particular situations especially when direct contact with live parts is allowed.

NOTE 2 The voltage limit should not be exceeded at any load between full load and no load when the source is a safety isolating transformer.

NOTE 3 "Ripple free" is an r.m.s ripple voltage of not more than 10 % of the d.c. component.

FRTBTS (très basse tension de sécurité)  
tension n'excédant pas 50 V en courant alternatif ou 120 V en courant continu lissé entre conducteurs ou entre un conducteur quelconque et la terre dans un circuit dont la séparation du réseau d'alimentation est assurée par des moyens tels qu'un transformateur de sécurité.

NOTE 1 Une tension maximale inférieure à 50 V en courant alternatif ou 120 V en courant continu lissé peut être spécifiée dans des situations particulières, plus spécialement lorsque le contact direct avec des parties actives est possible.

NOTE 2 Lorsque la source est un transformateur de sécurité, il convient que la limite de tension ne soit pas dépassée à toute charge comprise entre la pleine charge et à vide.

NOTE 3 «Lissé» est la valeur efficace d’une tension efficace ayant un taux d’ondulation ne dépassant pas 10 % de la composante continue.