IEVref:442-05-60ID:
Language:enStatus: Obsolete
Term: selectivity-limit current
Synonym1:
Synonym2:
Synonym3:
Symbol: Is
Definition: the current coordinate of the intersection between the maximum break time-current characteristic of the protective device on the load side and the pre-arcing (for fuses) or tripping (for residual current devices) time-current characteristic of the other protective device


Publication date:1998-11
Source
Replaces:
Internal notes:2012-12-19: Symbol incorrectly captured. Corrected for conformity with standard. JGO
CO remarks:
TC/SC remarks:
VT remarks:
Domain1:
Domain2:
Domain3:
Domain4: