IEVref:321-02-27ID:
Language:enStatus: Standard
Term: rated instrument limit primary current (IPL)
Synonym1:
Synonym2:
Synonym3:
Symbol:
Definition: the value of the minimum primary current at which the composite error of the measuring current transformer is equal to or greater than 10%, the secondary burden being equal to the rated burden